Authorize Yangzhou Chenglu Environmental Engineering Co., Ltd. to produce ASME boiler, pressure vessel and related products which meet GB150Ⅰ,Ⅱstandard.
Contact person: LiHongJian
Tel:
+86-514-87239999
+86-15805257759
Fax: +86-514-87237777
About Us
Chenglu Environmental Engineering Co., Ltd. has committed in wastewater treatment since 1983. Chenglu is one of the earliest manufacturers in sewage treatment equipment in China. With the development over 20 years, now we specialize in researching, designing and manufacturing of
sewage treatment equipment,
Oil Water Separator,Oil Filter, etc. Our products, Oil Water Separator, Sewage Disposal System,
Walnut Shell Filter,
Fiber Ball Filter,
Biological Aerated Filter,
Air Flotation,
Chemical Dosing Equipment, have been widely used in key construction projects.
Quick Links
Sewage Treatment Equipment Oil Water Separator Oil Filter Biofilter: Sewage Disposal System
Manganese Sand Filter
MSL Manganese Sand Filter
This type of MSL Manganese Sand Filter is designed to remove iron and Manganese ion in groundwater. Oxidize low valence iron and manganese ion to high valence, then adsorb and filter. Manganese dioxide is used as activator.
Features of MSL Manganese Sand Filter:
(1) Aeration system, no medicament is required.
(2) High decontamination due to the active filter film
(3) Without moving parts
(4) Low energy consumption and low cost
(5) Covers small area
Applications of MSL Manganese Sand Filter:
(1) Filter drinking water
(2) Advanced treatment of injection water in oil field
(3) The system with the limitation in iron ion and magnetic ion.
Process of Manganese Sand Filter:
You’d better offer the following materials:
a. Iron Content, Manganese Content, carbon dioxide Content, PH value, water temperature, Chroma, alkalinity, silicon dioxide content
b. The water output.
c. Water quality after treatment.
a. Intet: Fe2+≤6mg/L, outlet Fe2+<0.3mg/L.
b. Inlet: Mn2+≤1.5mg/L., Outlet Mn2+<0.1mg/L
c. Inlet: Fe2+=2mg/L, Mn2+=1mg/L
Outlet: Fe2+<0.3mg/L,Mn2+=0.1mg/L.
d. Inlet: Fe2+>2mg/L, Mn2+>1mg/L or Fe2+>10mg/L Mn2+>1.5mg/L
Outlet: Fe2+<0.3mg/L, Mn2+<0.1mg/L
Technical Data of MSL Manganese Sand Filter:
| Capacity |
5~70m3/h |
Cycle |
12-24h |
| Pressure |
0.6Mpa |
Backwash Intensity |
14-18L/sm2 |
| Temperature |
90°C |
Max pressure loss |
0.1Mpa |
| Filtration rate |
8-10m/h |
Backwash time |
10-15min |